Wrong Spacing Unit
Do not use the feet-based shortcut with centimeter spacing or the result will be wrong by a large factor.
Soil resistivity is one of the most important inputs for cathodic protection design, anode-bed evaluation, current distribution, and troubleshooting. The calculation is straightforward, but only when the probe spacing, resistance reading, and units are controlled.
ρ = 2πaR
or, when probe spacing is in feet:
ρ = 191.5 × a × R
| Symbol | Meaning | Common Unit |
|---|---|---|
| ρ | Soil resistivity | ohm-cm |
| a | Pin spacing | cm or ft |
| R | Measured resistance | ohms |
Use the Wenner soil resistivity calculation when evaluating soil conditions for galvanic anodes, impressed current anode beds, current requirement estimates, AC mitigation studies, or changes in CP system performance.
For certification study, the important skill is not only recalling the equation. You must also recognize what the instrument reading represents and keep the spacing unit consistent with the formula selected.
A Wenner four-pin test is performed with 5 ft pin spacing. The instrument reads 2.5 ohms. Estimate soil resistivity in ohm-cm.
ρ = 191.5 × a × R
ρ = 191.5 × 5 × 2.5
ρ = 2,394 ohm-cm
The estimated soil resistivity is approximately 2,394 ohm-cm.
If the pin spacing is entered in centimeters, use the 2πaR form. If the pin spacing is entered in feet, use the 191.5aR shortcut for ohm-cm. Mixing those approaches is a common source of large errors.
Use 2πaR with spacing in cm
Use 191.5aR with spacing in ft
Do not use the feet-based shortcut with centimeter spacing or the result will be wrong by a large factor.
Use the resistance reading from the instrument, not a potential reading or current value.
One resistivity value does not fully define the site. Layering, moisture, and depth matter.